INPUT | ||
Nominal voltage | 208/220/230/240Vac | |
Input voltage range | 110~300Vac (176~280Vac @ 100% load) | |
Frequency range | 40~70Hz  (50/60Hz Auto-Sensing) | |
Power factor | ≥0.99 | |
OUTPUT | ||
Output voltage | 208/220/230/240Vac | |
Power factor | 0.9 | |
Voltage regulation | ±1% | |
Output frequency | Line Mode | 46~54Hz or 56~64Hz |
Bat. Mode | (50/60±0.1%)Hz | |
Crest factor | 3:01 | |
Harmonic distortion (THDv) | ≤3% Linear load | |
≤5% Non linear load | ||
Transfer time | AC mode to Bat.Mode | 0ms |
Inverter to Bypass | 4ms (Typical) | |
Output waveform | Pure Sinewave | |
INDICATORS | ||
LED display | Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault | |
LCD display | Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, | |
Battery voltage,Inner temperature& Remaining battery backup time | ||
ALARM | ||
Battery mode | Beeping every 4 seconds | |
Battery low | Beeping every second | |
Overload | Beeping twice every second | |
Fault | Continously beeping | |
ENVIRONMENT | ||
Operating temperature | 0℃~40℃ | |
Storage temperature | -25℃~55℃ | |
Humidity range | 20~95%RH @ 0~40℃ (Non condensing) | |
Altitude | <1500m,derating required when>1500m | |
Noise level | <50db at 1 Meter | |
STANDARDS | ||
Safety | IEC/EN62040-1,IEC/EN62477-1 | |
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
Reviews